York PS8*DH Manuale Utente

Pagina di 8
279744-YTG-A-0407
Unitary Products Group
3
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
RATINGS & PHYSICAL / ELECTRICAL DATA
Models
Input
Output
Nominal
Airflow
Cabinet 
Width
Total Unit
Amps
AFUE
Air Temp. 
Rise
MBH
MBH
CFM
In.
 °F
PS8A12(N,L)040DH11
40
32
1200
14-1/2
9.0
80.0
20 - 50
PS8A12(N,L)060DH11
60
48
1200
14-1/2
9.0
80.0
25 - 55
PS8A12(N,L)080DH11
80
64
1200
14-1/2
9.0
80.0
35 - 65
PS8B16(N,L)080DH11
80
64
1600
17-1/2
12.0
80.0
25 - 55
PS8B12(N,L)100DH11
100
80
1200
17-1/2
12.0
80.0
40 - 70
PS8C16(N,L)100DH11
100
80
1600
21
12.0
80.0
25 - 55
PS8C20(N,L)100DH11
100
80
2000
21
14.0
80.0
25 - 55
PS8C16(N,L)115DH11
115
92
1600
21
12.0
80.0
35 - 65
PS8C20(N,L)115DH11
115
92
2000
21
14.0
80.0
30 - 60
PS8D20(N,L)130DH11
130
104
2000
24-1/2
14.0
80.0
40 - 70
Models
Input
Max. Outlet 
Air Temp
Blower
Blower 
Size
Max 
Over-Current 
Protect
Min. wire Size 
(awg) @ 75 ft 
one way
Operation
Weight
MBH
°F
Hp
Amps
In.
Lbs.
PS8A12(N,L)040DH11
40
150
1/3
6.2
10 x 8
20
14
100
PS8A12(N,L)060DH11
60
155
1/3
6.2
10 x 8
20
14
110
PS8A12(N,L)080DH11
80
165
1/3
6.2
10 x 8
20
14
120
PS8B16(N,L)080DH11
80
160
3/4
11.0
11 x 10
20
14
130
PS8B12(N,L)100DH11
100
170
1/2
7.0
10 x 8
20
14
125
PS8C16(N,L)100DH11
100
155
3/4
11.0
11 X 10
20
14
140
PS8C20(N,L)100DH11
100
155
1
12.2
11 x 11
20
12
140
PS8C16(N,L)115DH11
115
165
3/4
11.0
11 x 10
20
14
150
PS8C20(N,L)115DH11
115
160
1
12.2
11 x 11
20
12
150
PS8D20(N,L)130DH11
130
170
1
12.2
11 x 11
20
12
160