SS38 Direct Vent Gas Stove
VENTING INSTALLATION 
INSTALLATION FOR HORIZONTAL TERMI-
NATION 
1.  Determine the route your horizontal venting will take.
NOTE: The location of the horizontal vent termination on 
the exterior wall must meet all local and national building 
codes.
Snorkel terminations are available for terminations requir-
ing a vertical rise on the exterior of the building. Figures 
8 and 9. 
Follow the same installation procedures used for 
standard horizontal terminations. If installing the snorkel 
termination below grade (basement applications), you must 
provide proper drainage to prevent water from entering the 
snorkel termination. Figure 9. Do not back fill around the 
snorkel termination. 
12”
Minimum
ST1103
snorkel install
Snorkel
ST1103
Figure 8 - 
Snorkel Termination
12”
Minimum
ST1104
snorkel w drainage
Adequate 
Drainage
Snorkel
ST1104
Figure 9 - 
Snorkel Termination with Drain Pipe
2.  Rigid  vent  pipes  and  fittings  have  special  twist-lock 
connections. Assemble the desired combination of pipe 
and elbows to the appliance adaptor with pipe seams 
oriented towards the wall or floor.
  Twist-lock Procedure: The female ends of the pipes 
and  fittings  have  three  locking  lugs  (indentations). 
These  lugs  will  slide  straight  into  matching  slots  on 
the male end of adjacent pipes and fittings. Push the 
pipe sections together and twist one section clockwise 
approximately  one-quarter  turn  until  the  sections  are 
fully locked. Figure 10
FP1953
rigid pipe
Female Locking 
Lugs
Male Slots
FP1953
Figure 10 - 
Rigid Vent Pipe Connections
NOTE: Horizontal runs of vent must be supported every 
three (3) feet (914 mm). Use wall straps for this purpose.
3.  Attach vent pipe assembly to the stove. Set stove in 
front of its permanent location to insure minimum clear-
ances. Mark the wall for a 9Z\x" (241 mm) square hole 
(for noncombustible material such as masonry block or 
concrete, a 7Z\x" [190 mm] diameter hole is acceptable). 
Figure 11. The center of the hole should line up with 
the center line of the horizontal rigid vent pipe end. Be 
sure to allow for minimum rise.  Cut a 9Z\x"x9Z\x" (241 
X 241 mm) square hole through combustible exterior 
wall (7Z\x" [190 mm] diameter hole if noncombustible). 
Frame as necessary. Figure 11
W
ARNING
Do  not  recess  vent  terminal  into  a  wall  or 
siding.