external regulator
CHECK GAS TYPE
Use proper gas type for the stove you are installing. If you have conflicting gas type, do not install 
stove. See dealer where you purchased the stove for proper stove for your gas type or conversion 
kit.
INSTALL GAS PIPING TO STOVE / BURNER SYSTEM LOCATION
External 
Regulator 
100 lb. (min) 
Propane/LP 
Supply Tank 
Vent Pointing 
Down
STOVE INSTALLATION
W
ARNING
A qualified installer or service person must 
connect appliance to gas supply. Follow all 
local codes.
CAUTION
For  propane/LP  units,  never  connect  stove 
directly  to  the  propane/LP  supply.  This 
burner system requires an external regulator 
(not  supplied).  Install  the  external  regulator 
between  the  burner  system  and  propane/LP 
supply.
INSTALLATION ITEMS NEEDED
Before installing stove and burner system, make sure you have the items listed below.
  External regulator  
  Piping (check local codes) 
  Sealant (resistant to propane/LP gas) 
 
  (supplied by installer) 
  Test gauge connection* 
•  Sediment trap (recommended)
  Equipment shutoff valve* 
  Tee joint 
  Pipe wrench 
  approved flexible gas line with gas connector (if allowed by local codes — not provided)
A CSA design-certified equipment shutoff valve with 1/8" NPT tap is an acceptable alternative to test gauge 
connection. Purchase the CSA design-certified equipment shutoff valve from your dealer.
For propane/LP connections only, the installer must supply an external regulator. The external regulator will reduce 
incoming gas pressure. You must reduce incoming gas pressure to between 11 and 13 inches of water. If you do not 
reduce incoming gas pressure, burner system regulator damage could occur. Install external regulator with the vent 
pointing down as shown in Figure 27. Pointing the vent down protects it from freezing rain or sleet. 
FP1977
Figure 27 - 
External Regulator with Vent Pointing Down 
(Propane/LP Only)
CAUTION
Use  only  new  black  iron  or  steel  pipe. 
Internally  tinned  copper  or  copper  tubing 
can be used per National Fuel Code, Section 
2.6.3, providing gas meets hydrogen sulfide 
limits, and where permitted by local codes. 
Gas piping system must be sized to provide 
minimum  inlet  pressure  (listed  on  data 
plate)  at  the  maximum  flow  rate  (BTU/hr). 
Undue pressure loss will occur if the pipe 
is too small.
When  using  copper  of  flex  connectors  use  only  fittings 
approved  for  gas  connections.  The  gas  control  inlet  is 
3/8" NPT.