TB7220 COMMERCIALPRO™ PROGRAMMABLE THERMOSTAT
21
63-2635—03
To verify sensor resistance, remove one wire from one of the 
C7089U 60-in. leadwires. Use an ohmmeter to measure the 
resistance across the sensor. Then compare sensor accuracy 
with the temperature/resistance curve in Fig. 42.
C7189U Remote Indoor Temperature Sensor
Operation
When installed with Thermostat ISU 0340 set to 3, the remote 
inside temperature is displayed on the Thermostat Home 
Screen as Inside Temperature. The thermostat internal 
temperature sensor is not used.
The C7189U can be used to provide one remote sensor input 
or as a temperature averaging network with multiple C7189U 
Sensors connected, as shown in Fig. 29.
Checkout
For best results, allow C7189U Wall Mount Temperature 
Sensor to absorb the air moving through the room for a 
minimum of twenty minutes before taking a resistance 
measurement.
With an accurate thermometer (±1°F [0.5°C]) measure the 
temperature at the sensor location, allowing time for the 
thermometer to stabilize before reading.
To verify sensor resistance, remove one wire from one of 
C7189U wiring terminals. Use an ohmmeter to measure the 
resistance across the sensor. Then compare sensor accuracy 
with the temperature/resistance curve in Fig. 42.
Fig. 42. 10K ohm sensor resistance versus temperature.
T7770A Remote Temperature Sensor
Operation
When installed with Thermostat ISU 0340 set to 3 or 4, the 
remote inside temperature is displayed on the Thermostat 
Home Screen as Inside Temperature. The thermostat internal 
temperature sensor is not used.
The T7770A can be used to provide one remote sensor input 
or as a temperature averaging network with multiple T7770A 
Sensors connected, as shown in Fig. 26 through 28.
Checkout
For best results, allow T7770A Wall Mount Temperature 
Sensor to absorb the air moving through the room for a 
minimum of twenty minutes before taking a resistance 
measurement.
With an accurate thermometer (±1°F [0.5°C]) measure the 
temperature at the sensor location, allowing time for the 
thermometer to stabilize before reading.
To verify sensor resistance, remove one wire from one of the 
wiring terminals. Use an ohmmeter to measure the resistance 
across the sensor. Then verify the sensor accuracy with the 
temperature/resistance in Fig. 43.
Fig. 43. 20K ohm sensor resistance versus temperature.
TEMPERATURE (DEGREES)
o
F
-40
-20
0
20
40
60
80
100 120
-20
-30
-40
-10
40
RESIST
ANCE (OHMS)
10K OHM AT 
77
o
F (25
o
C)
220K
190K
160K
130K
100K
90K
60K
30K
o
C
M22823
0
10
20
30
50
0K
TEMPERATURE (DEGREES)
o
F
30
40
50
60
70
80
90
100 110
0
10
20
30
40
RESIST
ANCE (OHMS)
20K OHM AT 
77
o
F (25
o
C)
80K
70K
60K
50K
40K
30K
20K
10K
o
C
M5874A