Lucent Technologies Release 7 Manuale Utente

Pagina di 2657
DEFINITY Enterprise Communications Server Release 7 
Maintenance for R7r  
555-230-126  
Issue 4
June 1999
Maintenance Object Repair Procedures 
9-385
CARR-POW (Carrier Power Supply) 
9
FAIL
 
(cont’d.)
4. If the replaced OLS(s) still do not operate properly, then a circuit pack 
or a defective telephone connected to a circuit pack in the affected 
carrier could be causing an electrical load which is preventing the 
OLS from operating properly. Unseat all the circuit packs in the 
carrier, and reissue the recycle carrier command.
a. If the recycle passes, then the OLSs are healthy, and the problem 
is with one of the circuit packs. Reinsert the circuit packs one at a 
time. If the status LED shows red after reinserting a circuit pack, 
then replace the defective circuit pack. If the status LED still shows 
red, then remove the amphenol connector on the back of the slot 
containing this circuit pack and reissue the recycle carrier 
command. If the status LED shows green, then the problem is with 
one of the telephones or the wiring to one of the telephones on this 
slot.
b. If either OLS still shows a red status LED, then check for bent pins 
and cable placement in the affected carrier. There are failures that 
can occur on the SYSAM and EPN Maintenance circuit pack that 
will not be detected by their respective maintenance, but which 
will cause many, if not all, environment tests to fail. If many 
environment tests are failing, the suspect circuit pack, depending 
on the system configuration, should be replaced and the test 
rerun.
FAIL
DC POWERED SYSTEMS
There is a problem with one or both port carrier power supplies on the 
tested carrier.
1. For each port carrier power supply that has all status LEDs OFF, 
check the DC input to the port carrier power supply at the port carrier 
power supply outlet. If there is no DC, then check the appropriate 
circuit breakers for the affected port carrier power supply. If the circuit 
breaker has tripped, reset the circuit breaker. If the circuit breaker 
trips again or DC is not present at the port carrier power supply outlet, 
then there is probably a power wiring problem in the cabinet.
2. At this point, DC should be present at the port carrier power supply 
outlet. Use the recycle carrier UUC command (where 
UUC is the 
appropriate cabinet and carrier) in an attempt to bring back the port 
carrier power supplies for this carrier. If the test passes, the trouble is 
cleared. If the test does not pass, one port carrier power supply, or 
both, in the tested carrier is defective. If only one port carrier power 
supply is defective, then the status LEDs on the healthy port carrier 
power supply will light green for a moment. When the recycle test 
determines that both port carrier power supplies are defective, the 
software will turn off power to both the good and defective port carrier 
power supplies. This will cause the status LED(s) on the good port 
carrier power supply to light red.
Table 9-161.
TEST #127 OLS Query Test  — Continued
Error 
Code
Test 
Result
Description/ Recommendation
Continued on next page