Toshiba TOSVERT VF-AS1 Manuale Istruttivo
![Toshiba](https://files.manualsbrain.com/attachments/acaaaa9cc6b763ccfc72ced2ae95d9c94b8b8632/common/fit/150/50/8adbcbcd45c75dc53932fc9caf6f2740daed52d836b76efbd0162ac2599f/brand_logo.png)
E6581315
71
Appendix 5 Connecting for RS485 communication
Connector diagram for 2-wire RS485 communication
Connecting diagram for 2-wire RS485 communication
* Never use pin-7 (P11).
Master
RXD+/TXD+
RXD-/TXD-
SG
CN1
Pin-4
Pin-5
Pin-8
(Pin-3)
Straight
Straight
Terminating resistance
120Ω-1/2W
120Ω-1/2W
Straight
Slave
RXD+/TXD+
RXD-/TXD-
SG
Slave
RXD+/TXD+
RXD-/TXD-
SG
Slave
RXD+/TXD+
RXD-/TXD-
SG
Signal name
Pin number
Description
RXD+/TXD+
4
Same phase reception data (positive line)
RXD-/TXD-
5
Anti-phase reception data (negative line)
FWE
6
FEW (Do not connect the cable.)
SG
8
(3)
Ground line of signal data
PRG(TX)
2
PRG (Do not connect the cable.)
PRG(RX)
1
PRG (Do not connect the cable.)
P11
7
11V (Do not connect the cable.)
Pin-1
Pin-8
efesotomasyon.com -Toshiba inverter,drive,servo,plc