GE DEH-210 Manuale Utente

Pagina di 220
194  
  Appendix A: EPM 3720 Sliding Window Demand Keys
PMCS Interface Toolkit
Table A-1. EPM 3720 Sliding Window Demand Keys.
#1
#2
#3 & #4
Sliding Window Key Thumbwheel Settings
Class
Sub-class
Instance
Measurement
Supported Modes
4
3
00
Volts LN Average
HS STD TD SD PD
4
3
01
Volts LN Phase A
HS STD TD SD PD
4
3
02
Volts LN Phase B
HS STD TD SD PD
4
3
03
Volts LN Phase C
HS STD TD SD PD
4
3
04
Volts LL Average
HS STD TD SD PD
4
3
05
Volts LL Phase AB
HS STD TD SD PD
4
3
06
Volts LL Phase BC
HS STD TD SD PD
4
3
07
Volts LL Phase CA
HS STD TD SD PD
4
3
08
Amps Average
HS STD TD SD PD
4
3
09
Amps Phase A
HS STD TD SD PD
4
3
0A
Amps Phase B
HS STD TD SD PD
4
3
0B
Amps Phase C
HS STD TD SD PD
4
3
0C
Amps Neutral
HS STD TD SD PD
4
3
0D
Reserved
4
3
0E
Volts Imbalance (0-100)
HS STD TD SD PD
4
3
0F
Amps Imbalance (0-100)
STD TD SD PD
4
3
10
kW Total
HS STD TD SD PD HRS
4
3
11
kW Phase A
HS STD TD SD PD
4
3
12
kW Phase B
HS STD TD SD PD
4
3
13
kW Phase C
HS STD TD SD PD
4
3
14
kVAR Total
STD TD SD PD HRS
4
3
15
kVAR Phase A
STD TD SD PD
4
3
16
kVAR Phase B
STD TD SD PD
4
3
17
kVAR Phase C
STD TD SD PD
4
3
18
kVA Total
HS STD TD SD PD HRS
4
3
19
kVA Phase A
HS STD TD SD PD
4
3
1A
kVA Phase B
HS STD TD SD PD
4
3
1B
kVA Phase C
HS STD TD SD PD
4
3
1C
PF Total
STD TD SD PD
4
3
1D
PF Phase A
STD TD SD PD
4
3
1E
PF Phase B
STD TD SD PD
4
3
1F
PF Phase C
STD TD SD PD
4
3
20
Frequency
HS STD TD SD PD
4
3
21-23
Reserved
4
3
24
Phase Reversal (0 or 1)
HS STD
4
3
25-27
Reserved
4
3
28
VAUX
STD TD SD PD
4
3
29-2F
Reserved
4
3
30
I2T Avg. (0 = Off, 1= On)
HS
4
3
31
I2T Phase A (0=Off, 1=On)
HS
4
3
32
I2T Phase B (0=Off, 1=On)
HS
4
3
33
I2T Phase C (0=Off, 1=On)
HS
4
3
34-67
Reserved
4
3
68
V1 HD - K-Factor
STD TD SD PD