Diagnostics and Troubleshooting - User Interface 
134 
  HC900 Hybrid Controller Installation and User Guide 
Revision 5 
  
9/03 
Bad I/O Channel Diagnostics 
Below is a list of conditions that can cause a bad channel diagnostic. The associated function block’s I/O 
status will indicate the nature of the diagnostic described in the failure column. 
Table 29 - Bad Channel Diagnostics 
Module 
Type 
Failure Description 
User 
Action 
Burnout Failure 
The sensor – T/C, RTD, or mV source -- 
is failing burnout checks. 
1. 
Check terminal block 
connections 
2. 
Replace source 
element 
3. 
Replace card. 
Under range 
The signal at the terminals is less than 
10% below the range of the sensor. 
1. 
Check the signal level 
being applied to the 
terminals. 
2. 
Replace card. 
Over range 
The signal at the terminals is more than 
10% over the range of the sensor. 
1. 
Check the signal level 
being applied to the 
terminals. 
2. 
Replace card. 
AI 
Failing to 
convert 
When attempting to take a reading, the 
ADC fails. This could result if the 
incoming signal is either too large or 
small. It also could result if the ADC 
circuit is failing. If the problem is the ADC 
circuit, most likely other channels will 
have the same failure.  
 
1. 
Check the signal level 
being applied to the 
terminals. 
2. 
Replace card. 
AO 
Channel 
Failure 
The board indicates that the channel is 
failing to output the correct value. 
1. 
Check terminal 
connections. 
2. 
Replace module.