Testing the 
Interface 
Expander
To check the operation of the Interface Expander, perform 
the following steps in the order given.
1 Confirm that the UPS in on and that the battery is 
fully charged.
2 Verify that the Interface Expander has been 
installed, connected, and configured.
3 Confirm that all connected servers and devices are 
on and running their power management software 
with power management screens visible, if appli-
cable.
4 Confirm that the status LED on the Interface 
Expander is on, indicating normal operation.
5 Simulate a utility power failure.
6 Confirm that the status LED of the Interface 
Expander is mostly on with a single blink off, indi-
cating that the Interface Expander is sending an 
On Battery signal to the connected servers or 
devices. See “Status LED: Table 2” on page 6.
7 Confirm that all connected servers and devices 
have received the On Battery message from the 
Interface Expander.
8 Restore utility power.
9 Confirm that all connected servers and devices 
have received the message that utility power has 
been restored.
Note: To check the shutdown mode of your config-
uration, keep the utility power off long 
enough to allow all connected servers and 
devices to shut down. After all connected 
servers and devices have shut down, restore 
power and verify that they all restart.