MGE UPS Systems 4000 RT Manuale Utente

Pagina di 38
34008030EN/AA
 - Page 24
3. Operation
3.6 UPS shutdown
  
 
 
  
 
1 - Press the 
"
0
"
 button (28) more than 3s.
The buzzer beeps once, and the load is no 
longer protected by the UPS. It is powered 
via the Normal AC source. If the UPS is set 
in frequency converter mode, the 
equipments will not be powered.
If the Normal AC source is out of 
tolerance, the UPS will generate a 10ms 
output calibrated break.
2 - For a full shutdown of UPS and connected 
load, the upstream circuit breaker (not 
included) should be set to the 
"
0
"
 position.
ESC
I
O
34
22
28
33