Operation frequency
6.6.1 Starting frequency
H
: Starting frequency setting
• Function
The frequency set with H is put out as soon as operation is started.
Use the H parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a
value from 0.5 to 3Hz is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
Use the H parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a
value from 0.5 to 3Hz is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Starting frequency setting
0.5-10.0 (Hz)
0.5
6.6.2 Run/stop control with frequency setting signals
H
: Operation starting frequency
H
: Operation starting frequency hysteresis
• Function
The Run/stop of operation can be controlled simply with frequency setting signals.
[Parameter setting]
Title
Function
Adjustment range
Default setting
H
Operation starting frequency
0.0-HJ (Hz)
0.0
H
Operation starting frequency hysteresis
0.0-HJ (Hz)
0.0
0
A
B
100% Frequency command value
H
+ H
H
H
- H
HJ
The inverter begins accelerating after
the frequency setting signal has reached
point B.
Deceleration begins when the frequency
setting signal decreases below point A.
the frequency setting signal has reached
point B.
Deceleration begins when the frequency
setting signal decreases below point A.
Output frequency [Hz]