Toshiba VF-FS1 Manuale Utente

Pagina di 252
E6581381
E-13
5
5.5
Standard default setting
V[R
  : Default setting
Function
Allows setting of all parameters to the standard default setting, etc. at one time.
Note that HO, HOUN, H, H 
∼ H and H will not be reset to their factory
default settings.
Title
Function
Adjustment range
Default setting
V[R
Default setting
0: -
1: 50Hz default setting
2: 60Hz default setting
3: Standard default setting
(Initialization)
4: Trip record clear
5: Cumulative operation time clear
6: Initialization of type information
7: Save user-defined parameters
8: Call user-defined parameters
9: Cumulative fan operation time
record clear
0
+
This function will be displayed as 0 during reading on the right. This previous setting is displayed.
Example:        
+ V[R
 cannot be set during the inverter operating. Always stop the inverter first and then program.
Programmed value
50Hz default setting (V[R = )
Setting V[R at  causes all the following parameters to be set for operation using a base frequency of 50
Hz. (This does not change the setting of any other parameters.)
Parameter HJ, WN, XN, H, H, H, H: 50Hz
Parameter H: According to model
⇒ See page K-14.
50Hz default setting (V[R = )
Setting V[R at  causes all the following parameters to be set for operation using a base frequency of 60
Hz. (This does not change the setting of any other parameters.)
Parameter HJ, WN, XN, H, H, H, H: 60Hz
Parameter H: According to model
⇒ See page K-14.