Cabletron Systems 2H253-25R Manuale Utente

Pagina di 64
Installing the Device
3-4
Installation
Figure 3-1
Tabletop or Shelf Installation
3.3.2
Rackmount Installation
To install the 2H253-25R in a 19-inch rack, Cabletron Systems includes a strain-relief bracket for 
cable management and an accessory kit containing the rackmount brackets, and mounting screws 
to attach the rackmount brackets and strain-relief bracket.
Guidelines for the Rackmount Installation
The installation site must be within reach of the network cabling and meet the requirements listed 
below:
An appropriate grounded power receptacle must be located within seven feet of the location.
Maintain a temperature of between 5
°
C (41
°
F) and 40
°
C (104
°
F) at the installation site with 
fluctuations of less than 10
°
C (18
°
F) per hour.
!
CAUTION
To ensure proper ventilation and prevent overheating, leave a minimum clearance space 
of 5.1 cm (2.0 in) at the left, right, and rear of the 2H253-25R.
WARNING
Before installing the 2H253-25R
 
into a rack, ensure that the rack supports the device(s) 
without compromising the stability of the rack. Otherwise, personal injury and/or 
equipment damage may result.