Aube Technologies RC840 Dépliant

Pagina di 2
RC840
      400-276-000-C                    17/1/07                    1/2
The RC840 Electric Heating Relay is designed to control a line
voltage resistive load from a 24 V control signal. 
The RC840 operates silently and can be  installed in bedrooms, living
rooms, or any other occupied area without disturbing occupants. On
a call for heat, the relay is immediately activated; there is no delay.
This increases temperature control and comfort.
NOTE: 
Not recommended for fast-cycling modulated regulation. For fast-
cycling heating equipment, It is recommended to use the RT850 or RT850T
(integrated 24 V transformer) Solid State Relay.
I
The RC840 must be installed in an area where the temperature is
between -4°F and 140°F (-20°C and 60°C).
The RC840 can be installed on the side of an electrical box or a
distribution panel or inside the wiring compartment of an electric
baseboard.
All wiring must comply with national and local electrical code
regulations. 
Installation should be carried out by an electrician.
Disconnect power supply before installing the relay to prevent
electrical shock. 
n
Secure relay to the mounting surface using the two mounting 
brackets. Use the supplied lock nut to secure the relay to the 
junction box.
o
Wire the relay and connect according to typical wiring diagrams 
(refer to figures 1, 2 and 3).
p
Once mounting and wiring have been completed, return power 
to the heating system and test the installation. 
q
Increase the thermostat temperature to activate the relay. Allow 
system operation long enough to proof installation. Once 
installation has been proofed, set temperature to normal 
setpoint.
Figure 1 : 
Connection to a 2-wire low voltage thermostat using a 24 V 
external transformer
Figure 2 : 
Connection to a 3-wire low voltage thermostat using a 24 V 
external transformer
Figure 3 : 
Connection to a 2-wire low voltage thermostat using a 24 V 
external transformer and multiple relays
n
Application
1.
o
Installation
2.
On the side of 
an electrical box
Inside the wiring compartment 
of a baseboard
For proper installation, use
a screw and a washer.
p
Typical Wiring Diagrams
3.
You must provide an overload protection and disconnect as required.
External 24V 
transformer
Low-voltage 
2-wire 
thermostat
Load
Junction box
Black
Red
You must provide an overload protection and disconnect as required.
External 24V 
transformer
Low-voltage 
3-wire 
thermostat
Load
Junction box
Red
Black
You must provide an overload protection and disconnect as required.
Transformer VA output = RC840 Quantity x 1.2 VA
External 24V 
transformer
Low-voltage 
2-wire 
thermostat
Load
Load
Junction box
Junction box
Red
Black
Red
Black
RC840
Installation Guide
On/Off Switching Electric Heating Relay
400-276-000-C (RC840) ENG.fm  Page 1  Wednesday, January 17, 2007  3:48 PM