Fig. 7. W7750B,C construction in in. (mm). W7750C (shown) has three 4 to 20 mA analog outputs.)
Communications:
The W7750A,B,C Controller uses a Free Topology 
Transceiver (FTT) transformer-coupled communications port 
running at 78 kilobits per second (kbps). Using the 
transformer-coupled communications interface offers a much 
higher degree of common-mode noise rejection while 
ensuring dc isolation.
Approved cable types for L
ON
W
ORKS
 Bus communications 
wiring is Level IV 22 AWG (0.34 mm
2
) plenum or nonplenum 
rated unshielded, twisted pair, solid conductor wire. For 
nonplenum areas, use Level IV 22 AWG (0.34 mm
2
) such as 
U.S. part AK3781 (one pair) or U.S. part AK3782 (two pair). In 
plenum areas, use plenum-rated Level IV, 22 AWG (0.34 
mm
2
) such as U.S. part AK3791 (one pair) or U.S. part 
AK3792 (two pair). (See Tables 9 and 11 for part numbers.) 
Contact Echelon Corp. Technical Support for the 
recommended vendors of Echelon approved cables.
1
2
3
4
5
6
7
8
9
10
11 12
13
14
15
J3
E  
GND
LED BYPASS SNSR AI
GND
AI
GND
AI
GND
SET PT AI-1
OHM
AI-2
OHM
AI-3
V/mA
AI-4
V/mA
20VDC
OUT
L
ON
W
ORKS
 BUS
L
ON
JACK
31
30
29
28
27
26
25
24 23
22
21 20
19
18
17
16
DI-4
DI
GND
DI-3 DI-2
DI
GND
DI-1
VAC
24
VAC
24
COM
1
OUT
2
OUT
3
OUT
4
OUT
5
OUT
A0
1
A0
2
A0
3
5-3/16 (132)
5-5/8
(143)
3-1/16
(77)
2-1/8
(54)
6 (152)
M17490