NetShelter CX Enclosure: Installation and Customization
10
Rack PDU
The NetShelter CX Enclosure is provided with one Basic Rack PDU. The Rack PDU distributes power
to devices in the enclosure.
to devices in the enclosure.
AP9567 - North American
Outlets.
The Rack PDU has fourteen (14) NEMA 5015R outlets.
Power cord.
The 12-foot (3.66-meter) power cord terminates with a NEMA 5-15P plug.
AP9568 - International
Outlets.
The Rack PDU has fifteen (15) IEC-320-C13 outlets.
Power cord.
The 6.5-foot (1.98-meter) power cord terminates with a IEC-320-C14 plug.
Specifications
Electrical
AP9567
AP9568
Input connector
NEMA 5-15P
IEC-320-C14 inlet
Output connectors
(14) NEMA 5-15R outlets
(15) IEC-320-C13 outlets
Nominal input voltage
100-120 VAC
120-240 VAC
Acceptable input voltage
± 10% of nominal voltage
Input frequency
50/60 Hz