Move the locking clip away from the socket and reconnect the power cord.
Removing a Power Supply
First, make sure the power supply has been shut down. You can remove power from a
power unit via your system management software.
power unit via your system management software.
1.
Remove the power cord from the power supply unit.
2.
Figure 5-3. Power Supply Module
3.
Pull out the handle and remove the unit: the two-piece handle locks into the closed
position. To release the handle, squeeze together the two metal plates of the handle
with your thumb and fingers and then pull out.
position. To release the handle, squeeze together the two metal plates of the handle
with your thumb and fingers and then pull out.
5-2
Power Supply Fans
Each power supply unit has four rear fans. These fans are not hot-swappable. If one
fails, the power supply will continue to operate but you should replace the power supply
unit at the earliest opportunity. If two or more fans fail, the power supply unit will shut
down and the LED on the back will turn amber.
fails, the power supply will continue to operate but you should replace the power supply
unit at the earliest opportunity. If two or more fans fail, the power supply unit will shut
down and the LED on the back will turn amber.
Two-piece handle
Locking clip
AC input (C-20)
LED indicator