APC InfraStruXure Power Distribution Unit, 60 kW and 150 kW, 208 Volt Output
60 kW - 150 kW UPS/PDU/Distribution
THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE (CSI)
MASTERFORMAT. THIS SECTION MUST BE CAREFULLY REVIEWED AND EDITED BY THE ARCHITECT OR THE ENGINEER TO
MEET THE REQUIREMENTS OF THE PROJECT. COORDINATE THIS SECTION WITH OTHER SPECIFICATION SECTIONS IN
THE PROJECT MANUAL AND WITH THE DRAWINGS.
WHERE REFERENCE IS MADE THROUGHOUT THIS SECTION TO “PROVIDE”, “INSTALL”, “SUBMIT”, ETC., IT SHALL MEAN
THAT THE CONTRACTOR, SUBCONTRACTOR, OR CONTRACTOR OF LOWER TIER SHALL “PROVIDE”, “INSTALL”, SUBMIT”,
ETC., UNLESS OTHERWISE INDICATED.
THIS SECTION IS WRITTEN TO INCLUDE THE 2004 MASTERFORMAT AND THE 1995 MASTERFORMAT VERSIONS. WHERE
APPLICABLE, THESE ITEMS ARE BRACKETED AND, IN EACH CASE, UNLESS OTHERWISE INDICATED, THE FIRST CHOICE
APPLIES TO THE 2004 MASTERFORMAT AND THE SECOND CHOICE APPLIES TO THE 1995 MASTERFORMAT.
MASTERFORMAT. THIS SECTION MUST BE CAREFULLY REVIEWED AND EDITED BY THE ARCHITECT OR THE ENGINEER TO
MEET THE REQUIREMENTS OF THE PROJECT. COORDINATE THIS SECTION WITH OTHER SPECIFICATION SECTIONS IN
THE PROJECT MANUAL AND WITH THE DRAWINGS.
WHERE REFERENCE IS MADE THROUGHOUT THIS SECTION TO “PROVIDE”, “INSTALL”, “SUBMIT”, ETC., IT SHALL MEAN
THAT THE CONTRACTOR, SUBCONTRACTOR, OR CONTRACTOR OF LOWER TIER SHALL “PROVIDE”, “INSTALL”, SUBMIT”,
ETC., UNLESS OTHERWISE INDICATED.
THIS SECTION IS WRITTEN TO INCLUDE THE 2004 MASTERFORMAT AND THE 1995 MASTERFORMAT VERSIONS. WHERE
APPLICABLE, THESE ITEMS ARE BRACKETED AND, IN EACH CASE, UNLESS OTHERWISE INDICATED, THE FIRST CHOICE
APPLIES TO THE 2004 MASTERFORMAT AND THE SECOND CHOICE APPLIES TO THE 1995 MASTERFORMAT.
SECTION [26 26 53] [16471]
STATIC UNINTERRUPTIBLE POWER SUPPLY POWER DISTRIBUTION UNIT
PART 1 - GENERAL
1.1 RELATED
DOCUMENTS
A.
Drawings and general provisions of the Contract, including General Conditions,
[Division 01 - GENERAL REQUIREMENTS] [Division 1 - GENERAL REQUIREMENTS], and other
applicable specification sections in the Project Manual apply to the work specified in this Section.
[Division 01 - GENERAL REQUIREMENTS] [Division 1 - GENERAL REQUIREMENTS], and other
applicable specification sections in the Project Manual apply to the work specified in this Section.
1.2 SUMMARY
A.
Scope: Provide design and engineering, labor, material, equipment, related services, and
supervision required, including, but not limited to, manufacturing, fabrication, erection, and
installation for a power distribution unit (PDU) as required for the complete performance of the work,
and as shown on the Drawings and as herein specified.
supervision required, including, but not limited to, manufacturing, fabrication, erection, and
installation for a power distribution unit (PDU) as required for the complete performance of the work,
and as shown on the Drawings and as herein specified.
B.
Section Includes: The work specified in this Section includes, but shall not be limited to,
requirements for a complete power distribution system for powering IT loads.
requirements for a complete power distribution system for powering IT loads.
1.3 REFERENCES
A.
General: The publications listed below form a part of this Specification to the extent referenced.
The publications are referred to in the text by the basic designation only. The edition/revision of the
referenced publications shall be the latest date as of the date of the Contract Documents, unless
otherwise specified.
The publications are referred to in the text by the basic designation only. The edition/revision of the
referenced publications shall be the latest date as of the date of the Contract Documents, unless
otherwise specified.
B.
Electronic Industries Association (EIA):
1.
1.
EIA 310, "Racks, Panels, and Associated Equipment" (copyrighted by EIA, ANSI approved).
C.
International Organization for Standardization (ISO):
1.
1.
ISO 9001, "Quality Management Systems - Requirements."
2.
ISO 14001, “Environmental Management Systems - Requirements With Guidance for Use.”
D.
National Electrical Manufacturers Association (NEMA):
1.
1.
NEMA TP 1, "Standard for the Labeling of Distribution Transformer Efficiency.”
E.
Underwriters Laboratories, Inc. (UL):
1.
1.
UL 60950, “Standard for Information Technology Equipment.”