Location
Locate the thermostat or remote sensor about 5 ft (1.5m) 
above the floor on an inside wall where it is affected by 
freely circulating air at average room temperatures.
Mounting
1. Loosen the cover locking screw and remove the 
thermostat cover.
2. Run wire to the selected location; thread wire 
through the semicircular hole in the thermostat; and 
make connections to the T7047 (see the 
Wiring section).
3. Four mounting screws are provided, two self-
tapping type for wall mounting and two for outlet 
box mounting. Select the proper screws for the 
application.
4. If air drafts occur through the wall opening, 
eliminate with suitable material.
5. Fasten the T7047 on the wall or outlet box with 
screws through the thermostat mounting holes. See 
Fig. 2.
NOTE: Connect sensor wires to T-T terminals on 
the thermostat cover assembly.
6. Replace the cover and tighten the cover locking 
screw.
Fig. 2. Mounting the T7047.
Wiring
CAUTION
Electrical Shock or Equipment Damage 
Hazard.
Can shock individuals or short equipment 
circuitry.
Disconnect power supply before installation.
Fig. 3 through 7 show schematics and typical 
connections. Also refer to instructions supplied with other 
system components.
IMPORTANT
• All wiring must agree with applicable codes, ordi-
nances and regulations.
• To avoid electrical interference, which can cause 
erratic performance, keep wiring runs as short as 
possible and do not run thermostat wires adja-
cent to the line voltage electrical 
distribution systems.
• Use shielded cable (Belden type 8762 or 
equivalent for 2-wire and Belden type 8772 or 
equivalent for 3-wire).
• The cable shield must be grounded only at the 
controlled equipment case.
Fig. 3. Two T7047G Sensors providing a 
temperature-averaging network for a T7100/Q7100 
or T7300/Q7300 Thermostat/Subbase.
Fig. 4. Two T7047C Sensors and one T7047G Sensor 
providing a temperature-averaging network for a 
T7100/Q7100 or T7300/Q7300 Thermostat/Subbase.
THERMOSTAT
MOUNTING
TAB SLOT (2)
MOUNTING 
TAB 
(2 INSIDE 
COVER)
MOUNTING 
SCREW (2)
COVER 
LOCKING 
SCREW
OUTLET BOX
M17719
WALLPLATE
M3421
T
T
Q7300
T
T
T7047G1000
T7047G1000
T
T
M3418
T
T
Q7300
T
T
T7047C
T
T
T7047C
T
T
T7047G1000