Altronix AL400ULACMCB Dépliant

Pagina di 2
AL400ULACM
• Eight (8) independently controlled
fuse protected outputs.
AL400ULACMCB
• Eight (8) independently controlled
PTC protected outputs.
• The AL400ULACM / AL400ULACMCB converts an 115VAC 60Hz input 
into eight (8) independently controlled 12VDC or 24VDC Fail-Safe and/or 
Fail-Secure outputs with a total of 4 amp @ 12VDC or 3 amp @ 24VDC 
continuous supply current. Outputs are activated by an open collector sink or 
normally open (NO) dry trigger input from an Access Control System, Card 
Reader, Keypad, Push Button, PIR, etc. These units will route power to a 
variety of access control hardware devices including Mag Locks, Electric 
Strikes, Magnetic Door Holders, etc. The outputs will operate in both 
Fail-Safe and/or Fail-Secure modes. The units are designed to be powered by 
one common power source (factory installed) which will provide power for 
both the board operation and locking devices, or two (2) totally independent 
power sources, one (1) providing power for board operation and the other for 
lock / accessory power. The FACP Interface enables Emergency Egress, 
Alarm Monitoring, or may be  used to trigger other auxiliary devices. The fire
alarm disconnect feature is individually selectable for any or all of the 
eight (8) outputs.
• 12VDC or 24VDC outputs.
• 12VDC @ 4 amp supply current 
or 24VDC @ 3 amp supply current.
• Class 2 Rated power limited outputs.
• Power supply input options: 
a) One (1) common power input for ACM8/ 
ACM8CB and lock power (factory installed).
b) Two (2) isolated power inputs - One (1) to power 
the ACM8/ACM8CB and one (1) for lock 
accessory power, (external power supply 
is required). (Current is determined by the 
power supply connected, not to exceed a 
maximum of 10 amp total).
• Eight (8) Access Control System trigger inputs.
Input options:
a) Eight (8) normally open (NO) inputs.
b) Eight (8) open collector inputs.
c) Any combination of the above.
• Eight (8) independently controlled outputs.
Output options:
a) Eight (8) Fail-Safe and/or Fail-Secure power outputs.
b) Eight (8) form “C” 5 amp rated relay outputs 
(AL400ULACM only).
c) Any combination of the above (AL400ULACM only).
• Eight (8) auxiliary power outputs (unswitched) 
• Output ratings:
- Fuses are rated @ 3.5 amp (AL400ULACM).
- PTCs are rated @ 2.5 amp (AL400ULACMCB).
• ACM8 board main fuse is rated at 10 amp.
• Input 115VAC 60Hz rated @ 1.9 amp.
• Filtered and electronically regulated outputs 
(built-in power supply).
• Red LEDs indicate outputs are triggered (relays energized).
• Fire Alarm disconnect (latching or non-latching) is 
individually selectable for any or all of the 
eight (8) outputs.
Fire Alarm disconnect input options:
a) Normally open (NO) or normally closed (NC) 
dry contact input.
b) Polarity reversal input from FACP
signaling circuit.
• Alarm output relay indicates that FACP input 
is triggered (form “C” contact rated @ 1 amp 28VDC
not evaluated by UL).
• Green LED indicates when FACP disconnect 
is triggered.
• Built-in charger for sealed lead acid or gel type batteries. 
• AL400ULXB (Power Supply Board) 
maximum charge current .7 amp.  
• Automatic switch over to stand-by battery 
when AC fails.
• AC input and DC output LED indicators.
• Zero voltage drop when unit switches over to battery 
backup (AC failure condition).
• Short circuit and thermal overload protection. 
• AC fail supervision (form "C" contact). 
• Battery fail and battery presence supervision 
(form "C" contact).
• Enclosure accommodates up to two (2) 12AH batteries.
• Product weight: 
- AL400ULACM: 11.1 lbs.
- AL400ULACMCB: 10.1 lbs.
• Shipping weight: 
- AL400ULACM: 9.8 lbs.
- AL400ULACMCB: 11.4 lbs.
AL400ULACM, AL400ULACMCB 
Power Supply/Chargers w/Multi-Output 
Access Power Controllers   
Rev. DSAL400ULACM - A25F
Overview
Specifications