3.2.3.
Network error detection (c100 - c103, c523)
▼Display of trip information
err8
(Optional unit fault 1: 1BH): Network error stop
▼Related parameter
Title Function
Setting
range
Description
c100
Communication error
detection delay time
detection delay time
0.0-100.0 sec
The waiting time from when a network error occurs
can be adjusted. If a network error continues past
the time set in c100, it is recognized as a
communication error and the operation of the
inverter follows the setting of c101.
the time set in c100, it is recognized as a
communication error and the operation of the
inverter follows the setting of c101.
When normal communication returns during the
setting time, a communication error is not displayed
and operation is continued.
*The case of Modbus
and operation is continued.
*The case of Modbus
®
TCP protocol
The time-out detection time provides by c523
parameter.
Disconnection detection time =
parameter.
Disconnection detection time =
c523
(Time out) +
c100
(
Communication error detection delay time
)
*The case of EtherNet/IP
TM
protocol
-At I/O scanning and connected communication
Time-out time =
RPI 4 2
Connection Timeout Multiplier
[μs] + c100
(communication error detection delay time) [0.1s]
RPI: Request Packet Interval
RPI: Request Packet Interval
-At Unconnected communication
Time-out is not operating.
c101
Inverter operation at the
communications loss action
communications loss action
0-5
The operation of the inverter when the
communication fault occurs can be specified.
communication fault occurs can be specified.
c102
Preset speed operation
selection
selection
1-15
The operation frequency of the inverter when the
communication fault occurs can be specified. (Only
when c101 is set to 5)
communication fault occurs can be specified. (Only
when c101 is set to 5)
c103
Communication time-out
condition selection
condition selection
0-2
Select the communication time-out condition.
c523
Time out
0.0: Disable
0.5 - 60 sec.
0.5 - 60 sec.
The waiting time from the occurrence of the
network error to detection can be adjusted.
* When you are using unconnected communication
network error to detection can be adjusted.
* When you are using unconnected communication
of the EtherNet/IP protocol, time-out is not
detected.
detected.