UMG 96RM-M
Configuration
Applying the supply voltage
To configure the UMG 96RM-M, the supply voltage must 
be connected.
The level of supply voltage for the UMG 96RM-M can 
be found on the nameplate.
If no display appears, check the operating voltage 
to determine whether it is within the rated voltage range.
Current and voltage transformers
A current transformer is set to 5/5 A in the factory. 
The pre-programmed voltage transformer ratio only 
needs to be changed if voltage transformers are 
connected. 
When connecting voltage transformers, the measure-
ment voltage on the UMG 96RM-M nameplate must be 
observed!
c
Attention!
Supply voltages that do not correspond 
to the nameplate information can lead 
to device malfunction or destruction.
C
The adjustable value 0 for the primary  
current transformer does not produce 
any useful energy values and must not 
be used.
m
Devices, which are programmed to au-
tomatic frequency detection, need ap-
proximately 20 seconds to detect grid 
frequency. During this period, the mea-
sured values do not keep the confirmed 
measuring accuracy.