Installation Guide for Dimming and Switching Panels
Panel Model Number Guide
LCP128
TM
(LCP) (120 V
only)
See page 5 for 230/220-240 V
Modules: 
Quantity and Type
Prefix
Example
L C P - 2 X 2 D 1 A 4 T - 1 2 0 4 M L - 2 0
Prefix
LCP = LCP dimming panel
Module Types
_X _S _D _Q _A _M _F _T
List modules in the order shown above. Insert the
quantity before each module code. Omit codes for
modules not used in panel. See table below for limits
on numbers of modules per panel.
X = Four-Circuit Switching (Relay) (XP)
S = One-Circuit Dimming (1U)
D = Two-Circuit Dimming (2U)
Q = Four-Circuit Dimming (4U)
A = Four-Circuit Adaptive Dimming (4A)
M = Four-Circuit Motor (4M)
F = Four-Circuit Quiet Fan Speed (4FSQ)
T = 0-10 V, DALI (broadcast), DSI, and PWM 
Ballast Control (TVM)
Feed Voltage
120 for 120 V
Feed
Voltage
Branch Circuit
Breaker Rating
Feed
Type
Feed Type/Input Ratings
FT = Feed-through panel (circuit breakers not included) /
120 V
3ML = 1 phase 3 wire feed (split phase) / 120/240 V
4ML = 3 phase 4 wire feed / 120/208 V
Branch Circuit Breaker Rating
Omit for feed-through panels
20 for 20 A branch circuit breakers
Frequency - All Model Numbers and Voltages
50/60 Hz
Output (Load) Ratings
Module Type Rating
XP
16 A per circuit
1U, 2U, 4U
16 A per module
4A
16 A per module, 10 A per output
4M
16 A per module, 5 A per output 
(1/4 HP motor), 
1 motor per output
4FSQ
2 A per output (single ceiling fan)
TVM
50 mA per channel, 750 mA per system
Module Quantity Limits
Panel Size
Feed type
TVM
4A
4U
4M
Mini
Feed-through
NA
Any combination up to 3 modules
Mini
Feed-through
0-4
Any combination up to 2 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules 
Mini
Breakers
NA
Any combination up to 3 modules
Mini
Breakers
0-4
Any combination up to 2 modules; 
must have 1 4U module minimum; 
each 4U module can control only 2 TVM modules
Standard
Feed-through
NA
Any combination up to 9 modules
Standard
Feed-through
0-12
Any combination up to 8 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules
Standard
Breakers (main lugs)
NA
Any combination up to 9 modules
Standard
Breakers (main lugs)
NA
Any combination up to 7 modules
Standard
Breakers (main lugs)
0-12
Any combination up to 7 modules; 
must have 1 4U module minimum; 
each 4U module can control only 2 TVM modules
Standard
Breakers (main lugs)
0-12
Any combination up to 5 modules; must have 1 4U or XP module minimum;
each 4U or XP module can control only 2 TVM modules
Notes
• Consult Lutron for panels with custom breaker needs.
• TVM = 0 is a TVM-ready panel; TVM modules can easily be installed in the future.
• TVM = NA is not TVM-ready
XP
0
0
0
0