TROUBLESHOOTING
PROBLEM
POTENTIAL CAUSE
SOLUTION
Remote start system not 
working.
1. 
Low battery in remote start key 
fob
1. 
Replace batteries in key fob.
2. 
Exceeding the range of remote 
start key fob
2. 
Move closer to generator. Must be no more than 109 
yards (100 M) away.
3. 
Remote start key fob not 
programmed to generator
3. 
Program key fob to generator (see Programming the 
Generator for Remote Start on page 29)
.
Generator suddenly stops 
running.
1. 
Generator is out of fuel.
1. 
Check fuel level (see page 28). Add fuel if 
necessary.
2. 
The low oil shutdown switch 
has stopped the engine. 
2. 
Check oil level and add oil if necessary (see pages 
35 and 36).
3. 
Too much load
3. 
Restart the generator and reduce the load.
4. 
If trying 1-3 above does 
not solve the problem, the 
cause might be a fault in the 
generator.
4. 
Take the generator to your nearest authorized 
service dealer.
Engine runs erratic; does 
not hold a steady RPM.
1. 
Dirty air filter
1. 
Replace the air filter (see page 39).
2. 
Applied loads may be cycling 
on and off
2. 
As applied loads cycle, changes in engine speed 
may occur; this is a normal condition.
3. 
If trying 1-2 above does 
not solve the problem, the 
cause might be a fault in the 
generator.
3. 
Take the generator to your nearest authorized 
service dealer.