VACUUM CHECK
 
 
A sufficient level of vacuum is necessary for 
proper performance of the vacuum interrupters. 
Although vacuum leaks are rare, the vacuum 
integrity should be checked periodically.  The 
relationship between dielectric breakdown 
voltage of the contact gap and internal vacuum 
interrupter pressure has been found to be 
generally predictable. Therefore, vacuum 
interrupter integrity is checked by performing a 
high potential test across the open gap of the 
interrupter. 
 
TEST EQUIPMENT: 
 
Toshiba offers a compact vacuum checker (Type 
CI35-1D) which enables a quick and easy check 
on vacuum interrupter internal pressure. 
Alternatively, any commercially available AC high 
potential tester may be used which is capable of 
delivering at least 25 milliamperes at 22 kV for a 
period of one minute. 
 
PRECAUTIONS: 
 
Applying abnormally high voltage across a pair of 
contacts in vacuum may produce X-rays. The 
radiation may increase with the increase in 
voltage and/or decrease in contact spacing. X-
radiation produced during this test with 
recommended voltage and normal contact 
spacing is extremely low and well below the 
maximum permitted by standards.  As an 
additional safety measure, however, it is 
recommended  that all personnel keep at least 1 
meter (3.3 ft) away from the vacuum circuit 
breaker while this test is performed. 
 
 
Radiation exposure hazard. 
X-rays may cause illness or 
injury.  Stay at least 1 meter 
(3.3 ft) away from the circuit 
breaker during the vacuum 
check test . 
 
 
 
 
 
 
 
 
Hazardous voltages are 
present during dielectric 
testing which can result in 
severe injury or death.  
Only qualified personnel 
should conduct this testing. 
 
TEST PROCEDURE: 
 
1.  The circuit breaker should be disconnected 
from the main circuit and be in the OFF 
position. 
 
2.  Connect all the line side primary terminals 
together and to the output of the vacuum 
checker or AC hi-pot machine.  Connect all 
the load side primary terminals together and 
to the ground terminal of the vacuum checker 
or AC hi-pot machine. 
 
3.   Increase the voltage from zero to 22kV AC at 
a rate of approximately 2kV per second.  
Hold the voltage at this value for 1 minute 
and observe the current drawn by the 
interrupter. 
 
4.   Decrease the voltage back to zero. 
 
 
   