Toshiba Tortilla Maker HV6FS-MLD Istruzione Sull'Installazione

Pagina di 38
 
 
SPECIFICATIONS Page 
33 
 
 
 
Table 3  Circuit Breaker Ratings – Motor Stored Energy Operation HV6FS-MLD Type 
 
Rated Voltage  
kV, rms 
7.2 
4.8 
AC Withstand Voltage 
kV, rms 
22 – 1 Min. 
Basic Impulse Level 
kV 
60 
Maximum Continuous Current 
A, rms 
630 
Rated Frequency 
Hz 
50/60 
Rated Interrupting Current (0.15 P.F.) 
kA (Sym.), rms 
14 
16 
Rated Making Current 
kA (Peak) 
31.5kA 
Rated Short-Time Current (2 sec) 
kA, rms 
12.5 
Rated Interrupting Time (60Hz Basis) 
cycles 
Opening Time 
ms 
20 (Typical) 
Closing Time 
ms 
30 
Charging Time 
sec 
1.5 - 3 
Rated Control Voltage (Closing/Charging) 
DC 125 
Rated Control Voltage (Opening) 
DC 30, 125 
Rated Control Voltage (Undervoltage Trip) 
AC 120 
Operating Duty 
 
O - 1 min - CO - 3 min - CO 
Auxiliary Contacts 
 
2 N.O. - 2 N.C. 
Weight 
kg (lb.) 
38 (84) 
 
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net