Emerson Liebert MC Microchannel Outdoor Condenser 28 - 220kW Manuale Utente

Pagina di 68
Piping
Liebert
®
 MC
36
8. Verify the subcooling calculated from measured values at the evaporator against the subcooling 
reading of the Liebert MC control [menu ID F50 & F51]. If the subcooling calculated with gauges 
differs from the Liebert MC subcooling by more than 3°F (1.7°C), then adjust the charge amount 
to achieve the target subcooling per Table 13 based the Liebert MC control subcooling. Failure to 
check measured subcooling with refrigerant gauges vs. Liebert MC subcooling may result in an 
overcharged system. See Note below anTable 14 for corrections to Liebert MC subcooling that 
may be required based on condenser elevation above the indoor evaporator.
NOTE
To determine subcooling measurement, a liquid line pressure reading (at the factory-installed 
Schrader tap) needs to be measured along with obtaining a temperature reading on the liquid 
line. Convert the liquid line pressure reading into a temperature by utilizing a Pressure-
Temperature Guide or Table 15. The difference between this converted temperature and the 
actual temperature will determine the system’s subcooling. For R-407C make sure to use the 
saturated liquid temperature to calculate subcooling.
Table 13
Target subcooling for ambient outdoor temperature
Ambient Temp
°F (C°)
Subcooling
°F (C°)
0 (-17.8)
22 (12.0)
10 (-12.2)
22 (12.0)
20 (-6.7)
22 (12.0)
30 (-1.1)
22 (12.0)
40 (4.4)
22 (12.0)
50 (10.0)
21 (11.7)
60 (15.6)
19 (10.8)
70 (21.1)
17 (9.3)
80 (26.7)
13 (7.2)
90 (32.2)
9 (5.0)
95 (35.0)
7 (3.9)
100 (37.8)
5 (2.9)
105 (40.6)
3 (1.8)
110 (43.3)
1 (0.7)
125 (51.7)
0
DPN002411, Rev. 3
NOTE
The evaporator subcooling will be greater than the condenser subcooling when the Liebert MC 
is mounted higher than the indoor evaporator. Subcooling adjustment is needed when the 
Liebert MC is more than 40 ft. (12m) above evaporator.
NOTE
Subcooling should be viewed at the Liebert MC condenser for a minimum of 1 minute and the 
subcooling should be approximately ±2°F before recording subcooling to be compared against 
subcooling from the field refrigerant gauges and thermometers.