Avaya Media Gateway G700 Manuale Utente

Pagina di 768
Hardware installation for the G700 Media Gateway and S8300 Media Server
120 Installing and Upgrading the Avaya G700 Media Gateway and Avaya S8300 Media Server
 
If the ground block is not being used, simply: 
7.  Attach the Supplementary Ground Conductor to an approved ground.
8. Connect the AC power cable to the inlet receptacle on the rear of the chassis.
You have now mounted the fully equipped G700 Media Gateway in the rack, cabled units 
together as described in the planning documents, and connected to electrical ground 
conductors. When all the units are mounted, cabled, and grounded, you are ready to apply 
power.
Connecting AC Power
For North American installations, the AC Power Cord terminates on one end with a NEMA-15P 
plug to connect to the AC main socket-outlet at the wall. For installations in other regions, the 
plug to be used must comply with the local regulations and be marked as such, be suitable for 
the current and voltage being used, and contain an earthing pin for connection to ground at the 
AC mains socket-outlet through the cord.
To prevent accidental interruption of power to the G700 Media Gateway, do not connect the 
G700 Media Gateway to a switch-controlled AC wall socket-outlet. In addition, Avaya Inc. highly 
recommends that the customer use a UPS for back-up power. 
Advise your customer to verify through a licensed electrician that the ground connection at the 
AC outlet to be used is attached to an approved ground.
What are the G700 AC power requirements 
The G700 Media Gateway uses an auto-ranging 100-240 Vac power supply, 50 to 60 Hz, 5 A 
maximum at 100-120 Vac and 2 A maximum at 200-240 Vac. The AC power source must be 
single phase, 3-conductor (Line, Neutral and Ground) with a 15 A circuit breaker for 100-120 
Vac or a 10 A circuit breaker for 200-240 Vac.
Testing the AC Outlet
!
WARNING:
WARNING:
The following recommended test equipment, tests and diagrams are intended 
only for North American installations at 110 to 125 Volts AC. For installations in 
other regions, have a licensed electrician verify the ground and voltages.
!
WARNING:
WARNING:
If the AC outlet tests indicate that the power requirements are not met, your 
customer must contact a licensed electrician. DO NOT install the system until all 
requirements are met.