CONFIG - CYCLE TIME
The CYCLE TIME parameter sets the amount of time to wait before 
displaying the next bank measurement.  The parameter can be set to 
FAST, MEDIUM, or SLOW.
CONFIG - NUMBER OF CHANNELS
The unit can be configured to work for 1, 2, or 3 power bank devices.
Note that reducing the number of banks to 1 removes the total current 
monitoring processes.
CONFIG - CONTRAST
The CONTRAST feature allows the user to adjust the contrast of the LCD 
screen to a desired level.
CONFIG – SOFTWARE REV
Selecting the REV parameter will display the current revision of software 
loaded into the meter.  
CONFIG - METERING CALIBRATIONS
The unit’s onboard voltage and current monitoring devices require a 
two-step calibration procedure to achieve maximum accuracy.  Each 
power bank has adjustable parameters in the menu system for voltage 
and current.  This calibration is performed at the factory before shipment.  
Operational Control of PDU
Alarm Capabilities
Each power bank has four major alarm thresholds that can be adjusted.  
There is an upper and lower limit for input voltage.  There is also an 
upper and lower limit for distributed current.  An alarm is also signaled 
if the current reaches two minor limits: 80% of upper limit, 90% of upper 
limits.
If a major alarm threshold is surpassed the unit will respond by setting 
the power bank indicator LED to red and setting the audible alarm 
buzzer.
 
If a minor alarm threshold is surpassed the unit will toggle the LED 
indicator and audible alarm.  The 80% alarm toggles the LED and buzzer 
once per second.  The 90% alarm toggles twice per second.
If an alarm condition exists and the PDU is in monitor mode, the audible 
alarm may be silenced by pressing the Alarm Acknowledge button.  If the 
PDU is not in monitor mode and is in the system menu, select the Alarm 
Acknowledge menu item.  The audible alarm will remain silenced until 
another alarm threshold is exceeded.