Heatcraft Refrigeration Products H-IM-79E Manuale Utente

Pagina di 36
16
STATUS INDICATOR LED
 •  ERRORS  
E 1  -  Room temperature sensor shorted, open or not installed
   
E 2  -   Defrost temperature sensor shorted, open or not installed
   
E 3  -   Suction temperature sensor shorted, open or not installed
   
E 4  -   Suction pressure transducer shorted, open or not installed
   
E 5  -   Outdoor temperature sensor shorted
   
E 6  -   Low superheat during cooling
   
E 7  -   Compressor shutdown 
 
 
 
 
 
(high or low refrigerant pressure or low oil pressure) 
   
E 9  -  Multi-in/Multi-out wiring error
 •  OTHERS 
Coo -   Room Temperature sensor open or not connected  
 
 
 
 
 
(Instead of displaying box temperature)
   
Loc  -   Board is locked. Settings cannot be changed
   
UnL  -   Unlock the board settings
Low Ambient Operation
All units are shipped standard with Head Master valves. 
(Scroll compressor units have a 100 PSI Head Master 
valve and all other systems have a 180 PSI head master 
valve.) Condensing units with 
multiple condenser fans 
will have one or more fans cycle on Pressure Fan Cycling 
switch. 
An adjustable Time Delay relay, factory set at 1 minute, 
is wired across the Low Pressure switch (LPS). In cold 
ambient this allows time for the suction pressure to build 
up and prevent nuisance tripping of the LPS.
Pumpdown
At the end of each cooling cycle, when the box 
temperature is met, the Beacon system will pump down 
and shut off the compressor.
To pumpdown, the EEV closes and the compressor runs 
until one of the following occurs: 
 
• 
The low pressure switch opens 
 
• 
The suction pressure at the evaporator  
 
 
is 4 psig 
 
• 
A total of two minutes has elapsed 
Status Indicator LED
When any of these three conditions occurs the 
compressor will turn off and not restart until there is a 
call for cooling or a periodic pumpdown.
Periodic Pumpdown
While in the OFF cycle, if there isn’t a call for cooling 
(Box setpoint temperature is met) but: 
 
• 
The evaporator suction pressure has  
 
 
risen to 10 psig 
 
• 
The low pressure switch has closed 
The system will initiate pumpdown. This periodic 
pumpdown will occur at 4 minute intervals when these 
two conditions are met.