ELECTRICAL
Check Primary Supply voltage.
  If 208 V, change transformer wiring in the
  Cooler and Freezer to the 208 V tap
   
YES
•  Check Compressor Amps for COOLER and
  FREEZER compressors. Should match
  nameplate.
   
YES 
NO
PIPING
•  Is suction line trapped at the Cooler?
   
YES 
NO
•  Is suction line trapped at the Freezer?
   
YES 
NO
DRAIN LINES
•  Are drain lines sloped properly?
   
YES 
NO
•  Is drain line trapped outside the Cooler?
   
YES 
NO
•  Is drain line trapped outside the Freezer?
   
YES 
NO
•  Is heat tape wrapped along entire length of
  the drain line in the Freezer?
   
YES 
NO
•  Is heat tape plugged in and heating the drain
  line?
   
YES 
NO
INSULATION
•  Are Liquid lines fully insulated?
   
YES 
NO
•  Are Suction lines fully insulated?
   
YES 
NO
SETTINGS
•  Check Beacon II board settings for the
  following:
 
FREEZER
 Refrigerant Type 
R404A
  Box Setpoint Temp. 
-10°F.
  Superheat 
 
8°F.
  No. of Defrost / Day 
4
  Defrost End Temp. 
65°F.
 
COOLER
  Refrigerant Type 
R22
  Box Setpoint Temp. 
35°F.
  Superheat 
 
8°F.
  No. of Defrost/Day 
2
  Defrost End Temp. 
50°F. 
SYSTEM CHECKS
•  Check Compressor Superheat for the
  COOLER (Should be between 20°F. & 30°F.)
   
YES 
NO
•  Check Compressor Superheat for the
  FREEZER (Should be between 20°F. & 30°F.)
   
YES 
NO
•  Force unit into a Defrost Check heater amps.
  Should match nameplate amps.
   
YES 
NO
•  Check LPS Time Delay Relays. Should be
  set at 1 minute for both the COOLER and
  FREEZER.
   
YES 
NO
•  Check Low Pressure Switch on FREEZER. Should 
be set at 0 psig Cut-out/10 psig Cut-in.
   
YES 
NO
•  Did FREEZER and COOLER cycle off on LPS at 
Setpoint Temperature?
   
YES 
NO
•  Is the sight glass free of bubbles?
   
YES 
NO
•  Are the COOLER and FREEZER fans at proper 
speeds?
   
YES 
NO
•  Check system for refrigerant leaks. Are there any 
leaks on the COOLER, FREEZER, CONDENSING 
UNIT or INTERCONNECTING PIPING?
   
YES 
NO
•  Check system piping for unusual vibration or 
noise. Is there any unusual vibration or noise on 
the COOLER, FREEZER, CONDENSING UNIT or 
INTERCONNECTING PIPING?
   
YES 
NO
•  Start the FREEZER only. Does the compressor 
start and evaporator fans run for this FREEZER?
   
YES 
NO