  Getting Started
2.4. F3400/F1000 
Wiring
RLE Technologies recommends an 18AWG stranded copper wire for connection from each 
monitored point to a terminal block (TB) connection on the F3400/F1000. RLE recommends no 
more than 500 feet (152.4m) of wire at this specification. If longer runs are needed, please 
contact RLE Technologies for application guidance. Shielded twisted pair wiring is 
recommended for analog signal transmitters being wired outside of conduit runs and dropped 
ceiling applications.
2.4.1  Power Supply and Ground Connections
Connect an 18AWG ground wire from the ground terminal to a suitable earth ground. Plug the 
wall adapter into P1 and a UPS outlet as shown below. The wall adapter has a five foot power 
cord. RLE Technologies recommends powering the F3400/F1000 from a UPS supply to allow 
the F3400/F1000 to send alarm notification during a power outage.
Figure 2.1 24 VDC Power Supply Connection