  Configuration Menu
Column 1 = System Up Time.
Column 2 = Modbus Master Register Number.
Column 3 = Direction of Packet: OUT = Packet Sent from the F3400/F1000 (Master Request).
Column 4 = Modbus Packet.
4.10.4 Reset Modbus Port
This link allows users to reset the Modbus port so that the contents of the polling registers will 
be cleared.
4.10.5 F-Series Modbus Slave Register Map
Table 4.1 Output Registers
Register
Description
Range
40001-40032
Input #1-32 Value
0-65535
40033-40187
Reserved
40188-40193
MAC Address
0-65535
40194-40197
IP Address
0-65535
40198
Model No.
0-65535
40199
Firmware Version
0-65535
40200
Number of Alarms Present
0-65535
40201-40232
Input #1-32 Alarm Bitmap
40233-40400
Reserved
40401-40432
Input #1-32 Configuration
Table 4.2 Status Flags (Registers 40201-40232)
Bit
Description
00
1 = High1 Alarm
01
1 = Low1 Alarm
02
1 = High2 Alarm
03
1 = Low2 Alarm
04
1 = Digital Alarm
Table 4.3 Status Flags (Registers 40401-40432)
Integer
Description
0
Not Installed
1
Not Configured