70
• Release the REVERSE Push-button
• Does  PLC (Programmable Logic Controller) input L.E.D. #18 go “OFF”?
• If the answers to these questions are “YES,” wiring to the PLC is correct.
• If any answer to these questions is “NO,” refer to Probable Causes below
• Tumbler Forward Switch --- PB1
For quick check of the wiring of PB1 to the  PLC (Programmable Logic Controller) perform the following
test with the control voltage “ON” (“GREEN”  button).
• Press the FORWARD Push-button.
• Does  PLC (Programmable Logic Controller) input L.E.D. #17 light?
• Release the REVERSE Push-button.
• Does  PLC (Programmable Logic Controller) input L.E.D. #17 go “OFF”?
• If the answer to these questions are “YES,” wiring to the  PLC (Programmable Logic
Controller) is correct.
• If the answer to these questions are “NO,” refer to Probable Causes below
a) PROBABLE CAUSES;
1.  FUSE 4 ON MAIN ELECTRICAL PANEL
2.  FAULTY SWITCHES
3.  WIRING BACK TO  PLC (Programmable Logic Controller)
b) POSSIBLE SOLUTIONS;
1.  Check fuse blown indicator on fuse 4; replace fuse, if necessary and re-test.
2.  Check switches using an OHM meter; replace if necessary, and re-test.
3.  Refer to ADS-464 Pendant associated wiring diagrams for detailed assemblyand wiring information.
Check ALL circiuts back to  PLC (Programmable Logic Controller).
• ADS-464 PENDANT ASSEMBLY DIAGRAM
• ADS-464 ANNUNCIATOR, PENDANT, and UPPER RTD’S (Resistive Temperature Device)
WIRING DIAGRAM
• EMERGENCY STOP (E-Stop) SWITCH --- PB6
 If the “Emergency Stop” switch (pendant) does not respond: