Programming Function Blocks and Features 
 
Video Recorder – User Manual 
 
88
 
Table 4-6   Standard Algorithm Prompts (continued) 
 
 
Prompt 
Range/Selections 
Definition 
TEMPERATURE UNIT 
Select C for Degrees Celsius, F for 
Degrees Fahrenheit, K for Kelvin, R for 
Rankine, or NONE. 
Specifies the temperature units used for 
thermocouple, pyrometer, and RTD input 
types.  The default setting is F.  If you change 
the default, be sure to change the analog 
input’s RANGE LOW and RANGE HIGH 
values accordingly.  The instrument will not 
adjust these values by itself.   
Ignore the TEMPERATURE UNIT prompt or 
set it to NONE, if the analog input being 
programmed will not be used for temperature 
measurements. 
DIRECT/INDIRECT 
Select DIRECT for thermocouple, 
pyrometer, or RTD inputs.  Select INDIR 
(Indirect) for volt or millivolt signal inputs 
from linear or non-linear transmitters.  
Select SQRT (Square Root) for extracting 
flow measurements from a voltage input 
representing differential pressure 
measurements.  If SQRT is chosen, the 
RANGE LOW and RANGE HIGH must be 
adjusted to specify the upper and lower 
limits of the flow units span.  
Note that the term “direct” generally applies to 
input types where the sensors in direct 
physical contact with the monitored process 
are also in direct physical contact with the 
instrument terminal board.  The term “indirect” 
applies to inputs from transmitters since the 
sensors in direct physical contact with the 
monitored process are indirectly connected to 
the instrument through the transmitter circuitry 
and wiring. 
CIRCUIT LOW 
OFF or number 
Appears only if “INDIR” or “SQRT” was 
previously selected.  Is the actual low end 
value of voltage to be used for Indirect 
measurements. 
CIRCUIT HIGH 
OFF or number 
Appears only if “INDIR” or “SQRT” was 
previously selected.  Is the actual high end 
value of voltage to be used for Indirect 
measurements. 
ELECTRICAL UNITS 
Select whether the CIRCUIT LOW or 
CIRCUIT HIGH values specified are in 
units of VOLTS, MV (millivolts), or OHMS. 
Circuit low and circuit high units. 
LAG 
 0 seconds or OFF 
“LAG” is a time constant applied to the input 
measurement value. This provides digital 
filtering (LAG) to the measurement. 
Lag appears on menu only if EXPANDED 
INPUT is enabled under Enable Features in 
the Program menu. 
SAMPLE HOLD 
OFF, discrete parameter, 0, 1 
Holds Input. The input value is measured 
normally when this discrete is OFF and holds 
its last value when the discrete is ON(1).   
Hold appears on menu only if EXPANDED 
INPUT is enabled under Enable Features in 
the Program menu. 
FAILSAFE 
For thermocouples only, Upscale (UP), 
Downscale (DOWN) or None. 
Determines whether or not failsafe is active 
and, if so, which direction. 
CLAMPING 
HI RANGE clamps the input at the 
RANGE HIGH value. LO RANGE clamps 
input at the RANGE LOW value. RANGE 
clamps input over both the low and high 
range values. NONE gives no clamping. 
Clamps input at specified value. 
 
ATTENTION:  Clamping is not recommended 
for process variable inputs to control loops.