Honeywell VRX180 Manuale Utente

Pagina di 294
Programming Function Blocks and Features 
 
Video Recorder – User Manual 
 
104
4.10  Program Discrete Inputs 
Discrete Input function blocks are controlled by the on/off status of the input hardware.  The output of 
the function block, DIn OS, reflects the status of the associated input hardware.  This output DIn OS can 
be connected to other function blocks’ input parameters to trigger actions such as starting a profile or 
selecting a control loop’s Set point #1 or Set point #2, among many other possibilities. 
The Program Discrete Input menu item will appear if a DI/DO card is installed. 
Select a discrete input to program, then program the prompts in Table 4-14.  See Table 4-2 for 
additional prompts. 
Table 4-14   Discrete Input Prompts 
 
 
Prompt 
Range/Selections 
Definition 
ACTION STATE 
NORMAL, INVERT 
Determines whether the input will be normally closed or 
normally open when ON(1). To select closed when ON (1), 
enter NORMAL (not inverted). To select closed when OFF(0), 
enter INVERT (inverted). 
DELAY TIME 
Number of seconds 
When the DI is placed in its ON(1) state, the DI function will 
wait for the specified delay time before indicating the ON(1) 
condition as an output. If the DI "ON" state changes before 
the delay time expires, no ON output will be indicated. 
EVENT ENABLE 
NONE, RISING, FALLING, 
BOTH 
Determines whether changes in DI’s status can be recorded 
as events in data storage. 
NONE - status changes are not stored 
RISING - OFF(0)-to-ON(1) changes can be stored 
FALLING - ON(1)-to-OFF(0) changes can be stored 
BOTH - Both changes can be stored