Signal Select 
Selects one of 48 inputs based on the action and outputs it as CVn OV. 
Table 4-18 describes the Signal Select prompts.  See Table 4-2 for additional prompts. 
Table 4-18   Signal Select Prompts 
 
 
Prompt 
Range/Selections 
Definition 
OUTPUT LOW LIMIT 
OUTPUT HIGH LIMIT 
OFF or number 
Displayed output value will be clamped and will flash when 
these limits are exceeded. 
INPUT #1 - INPUT #48 
OFF, analog parameter, 
number 
Up to 48 input sources to be selected from according to the 
ACTION. 
ACTION 
HIGH 
Selects the highest value input. 
 
LOW 
Selects the lowest value input. 
 
AVG 
Averages the input values. 
 
MIDDLE 
Selects the middle (median) input value. If the number of 
inputs is even, selects the sum of the middle two input values 
divided by 2. 
 
F-GOOD 
(First Good) If inputs fail, selects the first good input to the 
function block.  For example, if inputs 1 and 2 fail, then input 
3 is selected. 
 
ANA-SW 
(Analog Switch) Selects an input equal to the value of the 
ANALOG SELECT parameter. 
 
DIS-SW 
(Discrete Switch) Selects Input #1 or #2 according to state of 
DISCRETE SELECT. 
ANALOG SELECT 
OFF, analog parameter, 
number 
Example: if ASEL=3, then Input #3 is selected. If ANALOG 
SELECT < 1, Input #1 is selected. The value of ANALOG 
SELECT is truncated to a whole number.  For example, if 
ANALOG SELECT is 3.55, the value is truncated to 3 and 
Input #3 is selected. 
DISCRETE SELECT 
OFF, discrete parameter, 
0, 1 
Selects Input #1 when DISCRETE SELECT is off (0); selects 
Input #2 when DISCRETE SELECT is ON (1).  Inputs 3-48 
are unused.