Honeywell VRX180 Manuale Utente

Pagina di 294
Programming Function Blocks and Features 
 
Video Recorder – User Manual 
 
112
Table 4-20   Compare’s Condition Type and Condition Time Prompts (continued) 
Condition type 
Application 
If this is true 
then CVn OS is 
PULSE 
Used for interfacing with slower 
circuits. 
On rising edge of Result, 
creates pulse length 
CONDITION TIME and ignores 
additional rising edges of Result 
within that CONDITION TIME. 
Result switches ON(1) for 
 
CONDITION TIME, then 
OFF(0). 
ON(1) for CONDITION TIME, 
then OFF(0).  During 
CONDITION TIME, any 
additional OFF(0)-to-ONs of 
Result are ignored. 
 
3 sec
Condition Type = Pulse
Condition Time = 3 seconds
3 sec
2 sec
If Result is:
Then CVn OS is:
3 sec
3.5 sec
Time 
 
 
Condition type 
Application 
If this is true 
then CVn OS is 
RT PULSE 
(Re-triggerable pulse) 
Used for slower circuits. 
Result switches ON(1) for 
 
CONDITION TIME, then 
OFF(0) 
ON(1) for CONDITION 
TIME, then OFF(0). 
 
Guarantees that CVn OS will be 
ON for CONDITION TIME after 
most recent rising edge of 
Result. 
Result switches ON(1) multiple 
times before CONDITION TIME 
expires 
ON(1) when Result first 
switches ON(1) and 
remains ON(1) until Result 
has not switched ON(1) for 
CONDITION TIME. 
 
 
Result switches ON(1) for 
 
CONDITION TIME, then 
OFF(0) 
ON(1) for CONDITION 
TIME then OFF(0). 
 
3 sec
If Result is:
Then CVn OS is:
Time 
Pulse is
re-triggered
4 sec
Condition Type = Re-triggerable Pulse