Interval Timer 
This timer counts down from the preset value in minutes.  This time remaining is CVn OV.  The timer 
has a single discrete output CVn OS which is ON(1) while the timer is actively counting or while RESET 
is ON(1), and OFF(0) while the timer has timed out to zero.  When RESET/RUN switches ON(1) the 
timer resets to the preset value; an ON(1) to OFF(0) transition starts the timer. 
Table 4-34 describes the Interval Timer prompts. See Table 4-2 for additional prompts. 
Table 4-34  Interval Timer Prompts 
 
 
Prompt 
Range/Selections 
Definition 
PRESET 
OFF, analog parameter, 
number 
Timer counts to zero from this number of minutes. 
RESET/RUN 
OFF, discrete parameter, 0, 1 
Controls the operation of the timer. 
RANGE LOW 
RANGE HIGH 
OFF or number 
Enter the output’s display limits.  Output is not clamped or 
flashed when it exceeds these limits.