Programming Function Blocks and Features 
 
Video Recorder – User Manual 
 
128
 Mass Flow 
By compensating for variations in fluid temperature and pressure, Mass Flow is used to obtain a more 
precise fluid flow measurement from an orifice plate developing a differential pressure. The output CVn 
OV is mass flow and is calculated from the following formula for U.S. Units Of Measurement: 
MF = FACTOR 1 x SQRT [DP INPUT x (PRESSURE INPUT+14.7) / (TEMPERATURE INPUT + 459)] 
where 
FACTOR 1 is calculated by user 
DP INPUT is differential pressure in inches of water  
PRESSURE INPUT is in PSIG  
TEMPERATURE INPUT is in °F 
Or, Mass flow is calculated from the following formula for International Units Of Measurement: 
MF = FACTOR 1 x .569 x SQRT [DP INPUT x (PRESSURE INPUT +101.4)/(TEMPERATURE INPUT + 273)] 
where 
FACTOR 1 is calculated by user 
DP INPUT is differential pressure in KPASCALS 
PRESSURE INPUT is in KPASCALS 
TEMPERATURE INPUT is in °C 
Table 4-37 describes the Mass Flow prompts. See Table 4-2 for additional prompts. 
 
Table 4-37   Mass Flow Prompts 
 
 
Prompt 
Range/Selections 
Definition 
OUT LOW LIMIT 
OUT HIGH LIMIT 
OFF or number 
Displayed output value will be clamped and will flash 
when these limits are exceeded. 
DP INPUT 
OFF, analog parameter, 
number 
Differential pressure input 
PRESSURE INPUT 
OFF, analog parameter, 
number 
Pressure input in PSIG or KPASCALS 
TEMP INPUT 
OFF, analog parameter, 
number 
Temperature in °C or °F 
UNITS OF MEASURE 
US or International 
Units of measure 
FACTOR 1 
OFF, analog parameter, 
number 
Flow factor for the particular installation