Programming Function Blocks and Features  
 
Video Recorder – User Manual 
 
147
4.16  Program Constants  
Constants can be programmed here and their values edited Online.  Select a constant to program. 
Table 4-52 describes the Constant prompts. See Table 4-2 for additional prompts. 
Table 4-52   Constant Prompts 
 
 
Prompt 
Range/Selections 
Definition 
VALUE OFF, 
analog 
parameter, number 
If a number, the Constant may be altered Online from the Data 
Entry menu.  If a parameter, this parameter can be directed by 
DESTINATION to override certain programmed values. 
INPUT LOW LIMIT 
INPUT HIGH LIMIT 
OFF or number 
Display limits (for when viewing Constant on trend display or on 
bar displays). 
DESTINATION 
 
See Destination defined on next page. 
 NONE 
No 
destination 
 LPGN LOOPGAIN1 
 LPPB LOOPPROP. BAND #1 
 LPRS LOOPRESET #1 
 LPRA LOOPRATE #1 
 LPRB 
LOOPn RATIO BIAS 
 LPIS LOOPSP INC SLEW LIMIT 
 LPDS LOOPSP DEC SLEW LIMIT 
 LPHS LOOPSP HIGH LIMIT 
 LPLS LOOPSP LOW LIMIT 
 AOIS AOINC SLEW LIMIT 
 AODS AODEC SLEW LIMIT 
 AOHS AOIN HIGH LIMIT 
 AOLS AOIN LOW LIMIT 
 AOIT AOIMPULSE TIME (type DAT) 
COMM CONSTANT 
Yes/No 
When enabled, any constant writes via modbus communication 
will only be written to the RAM copy of the configuration and not 
to the non volatile flash copy. 
When the unit cold starts, the constant values set up to be 
periodically written via communications will revert back to any 
value that was manually set via the local HMI. The local HMI will 
always write the constant value to the RAM and non volatile flash 
which will be preserved across a power cycle.