Honeywell VRX180 Manuale Utente

Pagina di 294
Setpoint Profiler 
 
Video Recorder – User Manual 
 
196
Editing Segments 
Use the following prompts to map out each segment’s value, time, and events.  Up to 63 segments are 
programmable per profile. 
Table 5-6   Edit Segments Prompts 
Prompt 
Range/Selections 
Definition 
NEXT SEGMENT 
 
Select this to edit the next segment. 
PREVIOUS SEGMENT 
 
Select this to edit the previous segment 
VALUE 
OFF or number 
This prompt is active for soak segments 
and value/duration ramp types.  Enter the 
value of the segment. 
AUX VALUE 
OFF or number 
This value is an auxiliary soak output of 
the profile.  The output is identified as 
SPn A1 and remains constant for the 
duration of the segment. 
TIME 
OFF or Positive number 
The purpose of the number entered here 
depends on the ramp type of the profile.  
See 4 types of ramp segments on page 
178 for details. 
GUAR SOAK #1 
ON or OFF 
ON means the profiler will Hold during this 
segment if deviation between PV #1 and 
the profiler output exceeds the 
guaranteed soak limits in Table 5-5.  OFF 
means the profiler will not Hold during this 
segment due to deviation. See 
Guaranteed Soak on page 182 for details. 
GUAR SOAK #2 
ON or OFF 
ON means the profiler will Hold during this 
segment if deviation between PV #2 and 
the profiler output exceeds the 
guaranteed soak limits in Table 5-5.  OFF 
means the profiler will not Hold during this 
segment due to deviation. See 
Guaranteed Soak on page 182 for details. 
EDIT EVENTS 
EVENT #1 
EVENT #16 
Enter the state of up to 16 discrete 
outputs of this segment.  These outputs 
can be used to trigger any action requiring 
a discrete signal, such as a relay or 
another function block. 
An event stays on or off for the entire 
segment. 
To trigger events in the middle of a 
segment, you must divide the segment 
into 3 segments.  See Segment Events on 
page 183 for details.