Honeywell VRX180 Manuale Utente

Pagina di 294
Online Operation Using Menus 
 
Video Recorder – User Manual 
 
235
7.6 Tune Loop 
This option lets you tune (change) various loop parameters online.  These tunable parameters depend 
on the loop type in use and are described in Section 4.8, Program Control Loops.  Also, the following 
menu choices are available. 
 
Table 7-9  Tune Loop Prompts 
Prompt 
Range/Selections 
Definition 
LOOP TYPE 
STD, ADV, SPLIT, ON OFF, 
CAS P, CAS S, RATIO, 
DIAT 
STD: Standard 
ADV: Advanced 
SPLIT: Split Output 
ON OFF: On/Off 
CAS P: Cascade Primary 
CAS S: Cascade Secondary 
RATIO: Ratio 
DIAT: DIAT 
PV 
Number 
Value of PV 
OUTPUT 
-100 to +100 
Loop output %. 
SETPOINT SOURCE 
SP1 or SP2 
Indicates which setpoint is being used by the loop.  SP1 must 
be a number; SP2 may be a number or a value from a 
function block (remote setpoint). 
Bold items are read-only 
 
 
TOGGLE SETPOINT 
SOURCE 
SP1, SP2 
Press Enter to change the Setpoint Source from SP1 to SP2 
or vice versa. 
SETPOINT #1 
Number 
Enter the new value of SP1. 
SETPOINT #2 
Number or parameter 
Enter the new value of SP2.  If SP2 is a remote setpoint you 
cannot change the value here. 
PROP. BAND #1 
 
See Gain #1. 
GAIN #1 
Enter a value of 0.1 to 200 
for Gain, or 0.5 to 1000.0 for 
Proportional Band. Enter 
OFF to allow integral only 
control. 
 
 
(Variable Gain1 or PB1 is 
available by programming a 
constant's Destination with 
GN or PB.  See Program 
Constants, Section 4.16.) 
Gain is the proportional gain entry for the control loop (The 
value entered here is the gain applied to the error signal to 
determine the loop output. For example, a 10% change in 
process variable (with respect to the input range) from a 
balanced condition will result in a 10% change in output, 
when a gain of 1.0 is used. Enter a starting value at initial 
configuration. The value may be altered Online for final loop 
tuning. If an indirect source is specified as in an adaptive 
gain configuration, the value can only be altered at the 
source. 
Gain and Proportional Band are interchangeable values 
(Proportional Band = 100/Gain). For loops with dual tuning, 
Gain 1 is the gain for the first set of tuning parameters. Gain 
2 is for the second set.