Diagnostic and error messages 
 
Video Recorder – User Manual 
 
251
9.  Diagnostic and error messages 
9.1 Diagnostic Messages 
The instrument executes diagnostic routines during instrument start-up and during maintenance 
procedures such as calibration. It also monitors online operation for both process faults and instrument 
errors. 
Error messages 
Table 9-1shows messages that may appear on the instrument displays if a diagnostic condition is 
detected, along with the action you should take.  
Table 9-1  Diagnostic Error Messages 
Message 
Description 
User action 
INPUT FAILURE 
The analog input is either open/shorted 
Check input devices for open or short. 
 
The analog input has been exposed to 
electromagnetic noise. 
See Section 2 for proper wiring 
techniques. 
 
The analog input is out of range 
Choose a higher range. 
FLOAT PT ERROR  A floating point calculation error has occurred. 
(divide by zero, underflow, overflow). 
Check Free Form Math and Math CV 
inputs for division by 0.  Also check for 
input values producing an underflow or 
overflow error (that is, calculation is not 
between -1x10
-38
 and -3x10
38
 or is not 
between 1x10
-38
 and 3x10
38
). 
CHECKSUM 
ERROR 
An error was detected in the database of one 
or more function blocks.  The affected 
function blocks are reset to their defaults. 
Inspect entire instrument configuration 
and reconfigure as needed. 
 
ATTENTION 
Be advised that the 
INPUT FAILURE
 diagnostic will continue to be displayed even after its cause has 
disappeared.  After verifying that this diagnostic’s cause has been corrected, you may clear the 
INPUT 
FAILURE
 message from all 
ON LINE
 screens by performing one of the following sequences of steps.  
1) Acknowledge the 
INPUT FAILURE
 diagnostic. 
From the 
ON LINE
 main menu, select 
ACCESS SUMMARIES
. Select 
DISPLAY DIAGNOSTICS
.  Use the 
<Up> and <Down> buttons to highlight the 
INPUT FAILURE
 diagnostic(s) that you wish to acknowledge and 
then press <Enter>.  Once the diagnostic has been acknowledged, it will still be listed in the 
DISPLAY 
DIAGNOSTICS
 screen but will no longer be displayed on any 
ON LINE
 screen. 
2) Delete the 
INPUT FAILURE
 diagnostic. 
From the 
ON LINE
 main menu, select 
ACCESS SUMMARIES
.  Select 
DELETE ALL DIAGNOSTICS
.  Once 
this menu choice has been executed,  all diagnostic messages will be deleted from the 
DISPLAY 
DIAGNOSTICS
 screen and will no longer be displayed on any 
ON LINE
 screen. 
During power-up, if an analog input is open or is out of range, the setpoint and process variable values 
will display OFF and the loop's AUTO mode is disabled.  Check connections to determine problem.  
During calibration if the input reference voltages supplied by the technician are outside acceptable limits 
a "CALIB FAIL" message will be generated.