Honeywell VRX180 Manuale Utente

Pagina di 294
Programming and Operating Concepts 
 
Video Recorder – User Manual 
44
 
Table 3-1   Button functions (continued) 
Symbol 
Name 
Function 
Operating mode in which 
function applies 
 
 
 
Program 
Online 
Maint 
 
Auto/ 
Manual 
•  In a loop display, toggles loop between 
Auto and Manual modes (loop's Force 
Remote Manual discrete must be OFF). 
•  In a loop display, toggles loop between 
Remote Manual and Manual modes 
(loop's Remote Manual discrete must 
be ON). 
•  Does not function if loop's Discrete vs. 
Key discrete is ON.  In this case, the 
button's functioning has been 
transferred to the loop's 
Auto/Manual Select discrete. 
 
#
 
 
 
#
 
 
 
#
 
 
ATTENTION 
The following keys are like Digital Inputs on the keypad of the instrument. They must be configured as part of 
the instrument’s function blocks in order to be active. 
F1
 
F1 
START 
•  When pressed, this key raises the SY1 
F1 signal for 1 machine scan cycle. 
•  For instruments with the Setpoint 
Profiler, user typically programs it to 
Profiler Start input or Totalizer Reset. 
 
#
 
 
 
 
F2
 
F2 
HOLD 
•  When pressed, this key raises the SY1 
F2 signal for 1 machine scan cycle. 
•  User typically programs it to Profiler 
Hold input (Use Edge/Level input 
selection) or to Totalizer Reset. 
 
#
 
 
 
 
F3
 
F3 
RESET 
•  When pressed, this key raises the SY1 
F3 signal for 1 machine scan cycle. 
•  User typically programs it to Profiler 
Reset input or Totalizer Reset. 
 
#
 
 
 
 
F4
 
F4 
•  When pressed, this key raises the SY1 
F4 signal for 1 machine cycle. 
 
#
 
 
F5
 
F5 
•  When pressed, this key raises the SY1 
F5 signal for 1 machine cycle. 
 
#