Programming and Operating Concepts 
 
Video Recorder – User Manual 
 
59
Table 3-9   Function Block Configuration Procedure (continued) 
Step 
Action 
Program the function block’s other items as desired.  Other items include decimal point positions, 
descriptor, tag, and various labels for identifying the function block. 
Repeat steps 1-4 for all desired function blocks until the instrument is configured. 
Example configuration 
Figure 3-10 shows a simplified configuration using typical function block connections.  Note that several 
parameters are left out to simplify the drawing and procedure.  
Table 3-10 describes how to program these connections. 
A I  1
L P   1
A O   1
P V
L P 1O V
IN P U T
S E T P O I N T # 1   =
1 5 0 0
A L   1
D O   1
A I1 O V
IN P U T
IN P U T
S E T P O I N T   =   5 0 0
A L 1 O S
T Y P E   =   C A T
T Y P E   =
  T y p e   J
D O 1O S
A O 1 O V
A O 1 B C
F E E D B A C K
K E Y
:
F U N C T IO N   B L O C K   T Y P E
IN P U T   P A R A M E T E R
F U N C T IO N   B L O C K   P A R A M E T E R
P A R A M E T E R   C O D E
A C T I O N   =   H I G H
A I1 O V
 
Figure 3-10   Example Configuration 
 
Table 3-10  Example Configuration Procedure 
Function block type (Full name 
as displayed in the Program 
menu

1. Select this menu item from 
the Program menu. 
2. Select this 
input parameter 
from the function 
block’s menu... 
...and program it 
with this output 
code.  See Section 
3.11 for details. 
3. Select this 
Function block 
parameter from the 
function block’s 
menu... 
...and program 
it with this 
choice.  See 
Section 3.12 
for details. 
AI 1 (ANALOG INPUT #1
-- --  TYPE 
TYPE 
LP 1 (LOOP #1
PV AI1 
OV 
SETPOINT#1 
1500 
 FEEDBACK 
AO1 
BC 
 
 
AL 1 (ALARM #1
INPUT AI1 
OV  SETPOINT 
500 
  
 
ACTION 
HIGH 
DO 1 (DISCRETE OUTPUT #1
INPUT AL1 
OS  -- 
-- 
AO 1 (ANALOG OUTPUT #1
INPUT LP1 
OV  TYPE 
CAT