9  PID CONTROL FUNCTION
9.8  Examples of Program
Program example 2
This is an example of the sample program for auto tuning (limit cycle method).
Use device
The content of the devices used for the program is as follows.
: This is an item not occupied.
*1 The setting is always necessary.
*2 When CH1 is used.
Item
Device
Setting value
During auto-tuning
During PID control
Target value (SV)
(s1)
D500
5000 (50.0)
Not used
Measured value (PV)
(s2)
SD6022
According to input value
Not used
Parameter
Sampling time (TS)
(s3)
D510
500 (500 ms)
Not used
Operation setting 
(ACT)
Operation direction
(s3)+1 b0
D511.0
1 (Backward operation)
Not used
Input variation alarm
(s3)+1 b1
D511.1
0 (Alarm is not provided)
Not used
Output variation alarm
(s3)+1 b2
D511.2
0 (Alarm is not provided)
Not used
Auto-tuning
(s3)+1 b4
D511.4
1 (AT is provided)
Not used
Upper and lower limits of 
output value
(s3)+1 b5
D511.5
0 (Setting is not provided)
Not used
Select auto-tuning mode
(s3)+1 b6
D511.6
1 (Limit cycle method)
Not used
Input filter constant (
)
(s3)+2
D512
0 (Input filter is not 
provided)
Not used
Proportional gain (KP)
(s3)+3
D513
According to auto-tuning 
result
Not used
Integral time (TI)
(s3)+4
D514
According to auto-tuning 
result
Not used
Differential gain (KD)
(s3)+5
D515
0 (Differential gain is not 
provided)
Not used
Differential time (TD)
(s3)+6
D516
According to auto-tuning 
result
Not used
Input variation (incremental) alarm set value
(s3)+20
D530
Not used
Not used
Input variation (decremental) alarm set value
(s3)+21
D531
Not used
Not used
Output variation (incremental) alarm set value
Output upper limit set value
(s3)+22
D532
Not used
Not used
Output variation (decremental) alarm set value
Output lower limit set value
(s3)+23
D533
Not used
Not used
Alarm output
Input variation (incremental) is 
exceeded
(s3)+24 b0
D534.0
Not used
Not used
Input variation (decremental) 
is exceeded
(s3)+24 b1
D534.1
Not used
Not used
Output variation (incremental) 
is exceeded
(s3)+24 b2
D534.2
Not used
Not used
Output variation (decremental) 
is exceeded
(s3)+24 b3
D534.3
Not used
Not used
PV value threshold (hysteresis) width (SHPV)
(s3)+25
D535
500 (5.0)
Not used
Output value upper limit (ULV)
(s3)+26
D536
2000 (2 second)
Not used
Output value lower limit (LLV)
(s3)+27
D537
0 (0 second)
Not used
Wait setting from end of tuning cycle to start of PID 
control (KW)
(s3)+28
D538
-50 (Wait is not provided)
Not used
Output value (MV)
(d)
D502
According to operation
Not used