Mitsumi electronic MELSEC FX1S ユーザーズマニュアル

ページ / 92
FX1S Series Programmable Controllers
Installation Notes 3
3-4
3.3
General Specifications
Table 3.3: General Specifications
*1 The criterion is shown in IEC61131-2.
*2 Do not use the PLC under pressure higher than the atmospheric pressure. Doing so may
damage the PLC.
Item
Description
Operating Temperature
0 to 55 °C (32 to 131 °F)
Storage Temperature
-20 to 70 °C (-4 to 158 °F)
Operating Humidity
35 to 85% Relative Humidity, No condensation
Storage Humidity
35 to 90% Relative Humidity, No condensation
Vibration Resistance
*1
 - Direct Mounting
10 - 57 Hz: 0.075 mm Half Amplitude
57 - 150 Hz: 9.8 m/s
2
 Acceleration
Sweep Count for X, Y, Z: 10 times (80 min. in each direction)
Vibration Resistance
*1
 - DIN Rail Mounting
10 - 57 Hz: 0.035 mm Half Amplitude
57 - 150 Hz: 4.9 m/s
2
 Acceleration
Sweep Count for X, Y, Z: 10 times (80 min. in each direction)
Shock Resistance
*1
147m/s
2
 Acceleration, Action Time: 11 ms
3 times in each direction X, Y, and Z
Noise Immunity
1000 Vp-p, 1microsecond, 30 - 100 Hz, tested by noise simulator
Dielectric 
Withstand Voltage
AC PSU: 1500 VAC > 1 min., tested between all points, terminals, and ground
DC PSU: 500 VAC > 1 min., tested between all points, terminals and ground
Insulation Resistance
5 M
Ω > at 500 V DC, tested between power terminals and ground
Ground
Grounding resistance 100
Ω or less
Working atmosphere
Free from corrosive or flammable gas and excessive conductive dust
Working altitude
<2000m
*2
Certification
UL/cUL (UL508)
EC Directive
EMC(EN61000-6-2, EN50081-2), LVD(EN61010-1)