CHAPTER 6 INSTALLATION AND WIRING
6
6.
2 W
iring
6.
2.
1 W
iring 
precaut
ions
6.2
Wiring
This section describes wiring of encoders and controllers to the high-speed counter module.
6.2.1
Wiring precautions
To obtain the maximum performance from the functions of the high-speed counter module and improve the system 
reliability, an external wiring with high durability against noise is required.
Here are some precautions when wiring encoders and controllers.
(1) Wiring
• Different terminals are prepared depending on the voltage of the signal to be input. Connecting to a terminal 
with a different voltage may cause malfunction of the module or failure of the connected devices.
• In 1-phase input, always connect a pulse input cable on the A-phase side.
• Install a fuse for each external terminal to prevent the external devices or module from being burnt out or 
damaged if a load shorts in an output circuit. The following fuses have been tested by Mitsubishi.
(2) Connectors for external devices
• Connectors for external devices must be soldered or crimped properly. A poor soldering or crimping may 
result in malfunction.
• Securely connect the connectors for external devices to the connectors of the high-speed counter module, 
and securely tighten the two screws.
• When removing a cable from the high-speed counter module, do not pull the cable by the cable part.  
Remove a cable supporting the connector part of the cable by hand. Pulling the cable being connected to the 
high-speed counter module can cause malfunction. In addition, a damage of the high-speed counter module 
or cables can result.
Fuse model name
Rated current
Contact
312.750
0.75A
Littlefuse KK
www.littelfuse.com
216.800
0.8A