Mitsubishi Electronics 0 ユーザーズマニュアル

ページ / 136
77
CHAPTER 8 FUNCTIONS
8
8.
Count
er F
u
nc
tion S
e
lect
io
n
8.
5.
2 C
ount
 error
8.5.2
Count error
A count error may occur when the selected counter function is performed by external input (A voltage is applied to the 
function start input terminal.) or by a program (CH Counter function selection start command (Y6, YE) is turned on).
The following describes how to calculate the count error.
(1) Count error (maximum) due to a delay of response to an external input
(2) Count error (maximum) when the selected counter function is performed by a 
program
(3) Count error (maximum) due to an internal clock delay when the sampling 
counter function or the periodic pulse counter function is performed
1 [ms]
1000
[s]      Pulse input speed [PPS]      Multiplication [count]
1 scan time [ms]
1000
[s]      Pulse input speed [PPS]      Multiplication [count]
Sampling/periodic time setting value      10 [ms]
1000
[s]
    Pulse input speed [PPS]      Multiplication [count]
Error in design, 100 [ppm]
1000000
=
Pulse input speed [PPS]     Multiplication [count]
1000000
(Sampling/periodic time setting value 
(unit: 10ms))